MDC500 · AI INFERENCE · 300–500 KW IT LOAD

Modular infrastructure for your AI inference servers.

The MDC500 AI inference data center brings power, cooling and IT space together for NVIDIA H200 and RTX PRO 6000 Blackwell inference systems. Select the configuration around your servers and site.

300–500 kW
Target IT-load range
10 × 42U
Air-cooled reference rack positions
Up to 50 kW
Per rack in the air-cooled reference
3
Technical modules in the issued air-cooled design
H200 / RTX PRO 6000
Target inference equipment

Infrastructure for AI inference workloads.

The selected servers determine rack power, airflow, network and service access. MDC500 coordinates those requirements in a modular facility.

The issued air-cooled design supports ten racks and up to 500 kW IT load. An immersion configuration needs a separate review of the server and cooling interfaces.

Run H200 and RTX PRO 6000 Blackwell inference systems.

Start with the server model and deployment plan. Rack geometry, power and cooling limits are checked against the chosen equipment.

Applications can include:

01

AI inference and selected GPU compute

02

Engineering and scientific HPC

03

Rendering and visualisation

04

Dense private cloud and virtualised infrastructure

05

Storage and data-processing clusters

For larger rack-scale AI clusters, compare MDC2000.

Cooling for the selected inference configuration.

Air cooling

Air-cooled servers with rear-door heat exchange in the issued reference design.

Immersion by project

Project-specific option, subject to server compatibility and a dedicated thermal and service design.

01

The servers remain air cooled.

IT equipment draws conditioned air through the rack.

02

The rear door captures exhaust heat.

Active fan modules move hot server exhaust across a chilled-water coil.

03

The closed loop carries the heat away.

Pumps, buffer capacity, isolation valves, filtration, instrumentation and controls circulate chilled water.

04

The external plant rejects the heat.

Three 200 kW modular air-cooled chillers stage with load and use free cooling when ambient conditions allow.

The issued design keeps servers air cooled and uses rear-door heat exchangers to move exhaust heat into a closed cooling loop. Immersion is a separate project option; it requires compatible equipment and its own cooling and service design.

The air-cooled reference: three coordinated zones.

The issued design separates the power equipment, ten-rack IT area and cooling services. Its component ratings and geometry apply to that configuration.

  1. 01

    Electrical & energy zone

    Switchgear, scalable modular UPS, batteries and AC distribution. Multiple utility or generator inputs and independent A/B rack paths are coordinated to the project power design.

  2. 02

    IT zone

    Ten 42U rack positions, each 800 × 1,200 mm, with active rear-door heat exchangers and independent rack distribution.

  3. 03

    Thermal & services zone

    Hydronic equipment, filtration, controls, fire-protection interfaces, security and technical access.

The project defines redundancy, fire protection, access and the acceptance tests for the selected configuration.

Scale inference capacity in planned phases.

Repeated 500 kW reference units provide a route to staged expansion. Plan shared power, cooling and connectivity with the first deployment.

Capacity planMDC500 unitsRack positions
500 kW110
1 MW220
2 MW440
Multi-MWRepeat standard units+10 per unit

The table shows repeated units of the issued air-cooled design. Other rack populations and immersion configurations follow their own engineering and capacity plan.

A/B power at the rack. Resilience designed end to end.

MDC500 supports multiple utility or generator inputs, online double-conversion UPS, scalable power modules and independent A/B rack delivery.

The project decides how those elements work together. A/B rack feeds alone do not establish 2N, concurrent maintainability or Tier certification. The design has to trace every path from source to rack.

Use the climate to reduce cooling energy.

The air-cooled reference uses modular chillers with free-cooling capability. When the ambient conditions allow, free cooling reduces compressor operation.

We model seasonal performance for the site climate, IT load, cooling temperatures and controls.

Factory integration for the selected inference configuration.

  1. 01

    Define the rack population.

    Hardware, dimensions, peak loads, airflow and growth.

  2. 02

    Freeze the interfaces.

    Power, chilled water, heat rejection, controls, fire protection, network, civil works and site access.

  3. 03

    Assemble the selected configuration.

    Integrate the agreed electrical, cooling and control systems in the factory.

  4. 04

    Complete factory acceptance testing (FAT).

    Execute the agreed inspection and functional test scope.

  5. 05

    Install at site.

    Position and interconnect the modules and external plant.

  6. 06

    Complete SAT and commissioning.

    Retest transported connections and the assembled facility before handover.

Factory work and site preparation can run in parallel. The programme still depends on equipment availability, site readiness, transport, permits and final configuration.

Issued air-cooled reference configuration

Reference IT-load capacity
500 kW
Rack configuration
10 × 42U positions, 800 × 1,200 mm
Maximum rack load
Up to 50 kW
Architecture
3 transportable technical modules operating as one system
Rack cooling
Active rear-door heat exchangers; IT remains air cooled
Water system
Closed-loop chilled-water distribution
Heat rejection
3 × 200 kW modular air-cooled chillers with free-cooling capability
Power
Multiple utility/generator inputs; online double-conversion modular UPS; independent A/B rack paths
Batteries
Lithium-ion option
Redundancy
Configurable 2N or N+1 for critical systems, subject to project design
Fire resistance
E60 / I60
Expansion
Repeatable 500 kW increments
Acceptance
Factory pre-integration and testing, followed by site acceptance and commissioning

What the site must provide

  • Confirmed power sources and upstream protection
  • Foundations for the selected modules and external heat-rejection equipment
  • Delivery, crane and maintenance access
  • Fibre and communications
  • Hydraulic and electrical interconnection routes
  • Ambient and environmental design conditions
  • Drainage, water-quality and freeze-protection strategy where applicable
  • Local fire, security and permitting coordination

Frequently asked questions

What AI workloads is MDC500 designed for?

MDC500 targets 300–500 kW IT-load deployments for AI inference using selected NVIDIA H200 or RTX PRO 6000 Blackwell systems. It supplies the facility infrastructure around those servers. The equipment list, rack heat loads and chosen cooling architecture determine the final configuration.

How many racks and what rack density does MDC500 support?

The issued air-cooled MDC500 reference has ten 42U rack positions and supports up to 50 kW per rack. The final rack schedule assigns compute, networking and storage equipment within the approved total IT load. A different cooling configuration needs its own equipment and layout review.

Does MDC500 use air-cooled servers or direct-to-chip liquid cooling?

The issued MDC500 reference keeps the servers air-cooled. Active rear-door heat exchangers capture rack exhaust heat and transfer it into a closed chilled-water loop, served by external air-cooled chillers with free cooling. Water in the facility cooling circuit does not mean liquid runs through the servers.

Can MDC500 be configured for immersion cooling?

Immersion is a separately engineered project option. The selected servers, dielectric fluid, tanks, service procedures and external heat rejection must be compatible. It should not be treated as a direct replacement for the ten-rack air-cooled reference or as a guarantee that any H200 or RTX PRO server can be immersed.

What are the water requirements for the MDC500 air-cooled design?

MDC500's rear-door heat exchangers use a closed chilled-water circuit with external air-cooled chillers. Water quality, initial filling, treatment, freeze protection and maintenance are defined for that circuit and the installation climate. The project specification establishes the actual water-service requirements.

What space and utility connections does MDC500 need?

The reference design brings three transportable technical modules together into one operational facility. Plan foundations and access for those modules and the external heat-rejection equipment, plus power, fibre and interconnection routes. The issued project layout defines delivery access, maintenance clearances and final loads.

Can multiple MDC500 units form a larger inference facility?

MDC500 can be deployed as repeated units for phased growth. The campus plan must also provide sufficient incoming power, external cooling, networking and service access for the additional capacity. The operating sequence and any effect on existing equipment are part of the expansion design.

What determines MDC500 cost and delivery time?

Server heat loads, the cooling configuration, electrical resilience, UPS and battery scope, site works and installation responsibilities all affect the quote. The schedule separates design, procurement, factory testing, transport and commissioning. Equipment availability and site readiness determine the project dates.

Tell us what your inference deployment needs.

Send the server configuration, intended IT load and location. We will assess the product fit and cooling option.

Contact form

Preview build: this form is not connected yet, so nothing was sent.